Description SolarBOS ReCombiners are used to combine the outputs of several source circuit combiners before connecting to the inverter. Covering a range of input configurations and fuse sizes, all ReCombiners are ETL listed to UL 1741. Features: * 5 x single positive input terminals (fused) sized for #6-350mcm conductors * 5 x single negative input terminals sized for #6-350mcm conductors * Output terminals are sized for #2-600mcm conductors (4 positive & 4 negative) * Ground terminals for 6x #14-2/0 and 1 x #6-350mcm grounds * Includes touch safe protective cover * Cover doors with poured-in-place seamless gaskets * Configured for both positive and negative grounded arrays * Optional configurations for floating PV arrays * Clean design for ample wiring room * Optional current monitoring with ModBus I/O modules * Optional Ground Fault Detection & Interruption (GFDI) Sensors * Optional Transient Surge Suppression Specification: * Fuse Ampacity: 110-200 Amps * Input Terminals*: #6-350 * # of Circuits: 2 to 10 @ Output Terminals*: 4 x #2-600 @ Dimensions(H.W.D. in.): 42x36x8 @ Approximate Weight (lbs): 155 * # of Circuits: 11 to 13 @ Output Terminals*: 6 x #2-600 @ Dimensions(H.W.D. in.): 42x36x8 @ Approximate Weight (lbs): 180 * # of Circuits: 14 to 16 @ Output Terminals*: 8 x #2-600 @ Dimensions(H.W.D. in.): 48x36x8 @ Approximate Weight (lbs):200 * Max Output Current(Continuous): 2560 Amps * Voltage: 600 or 1000 VDC * Current Sensors**: Up to 200 Amps * NEMA Ratings: 3R / 4 / 4X